Your cart is empty

3RK3111-2AA10 MSS 3RK3, CENTRAL MODULE BASIC

Part No.:
3RK3111-2AA10
Manufacturer:
Weight:
0.3kg
Product Range:
Industrial Controls

Product Information

SIRIUS,CENTRAL MOD. 3RK3 BASIC FOR MODULAR SAFETY SYSTEM 3RK3 4/8 F-DI, 1F-RO, 1 F-DO, 24V DC PARAMETERIZABLE VIA SW MSS ES WIDTH 45MM SPRING-LOADED TERMINAL UP TO CATEGORY 4 (EN954-1) UP TO SIL3 (IEC 61508) UP TO PERFORMANCE LEVEL E (ISO 13849-1)
General technical data:
Product brand nameSIRIUS
product designationModular Safety System 3RK3
Design of the productcentral module - basic
Protection class IPIP20
Resistance against shock15g / 11 ms
Degree of pollution3
Built in orientationvertical
Installation altitude / at a height over sea level / maximumm2,000
Ambient temperature
  • during operating
°C-20…60
  • during storage
°C-40…85
  • during transport
°C-40…85
Relative humidity
  • during operating phase
%95…10
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-42 kV (power ports)
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-52 kV
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-51 kV
Electrostatic discharge / according to IEC 61000-4-24 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling / according to IEC 61000-4-310 V/m, 3 V/m, 1 V/m
Impulse voltage resistance / rated valueV2,500
Insulation voltage / rated valueV300
Item designation / according to DIN 40719 extendable after IEC 204-2 / according to IEC 750K
Item designation / according to DIN EN 61346-2K
Product function
  • EMERGENCY STOP function
Yes
  • protective door monitoring
Yes
  • protective door monitoring with tumbler
No
  • muting, 2 sensor parallel
No
  • muting, 4 sensor parallel
No
  • muting, 4 sensor sequential
No
  • monitoring parameterizable
No
  • evaluation: contact-free acting protection device
Yes
  • evaluation: selector switch
Yes
  • step mat monitoring
Yes
  • evaluation: two-hand control panel
Yes
  • evaluation: enabling switch
Yes
  • monitored start-up
Yes
Protocol / will be supported / PROFIBUS DP protocolNo
Protocol / optional / will be supported / PROFIBUS DP protocolYes
Control circuit:
type of voltageDC
Control supply voltage / 1 / for DC / rated valueV24
Operating range factor control supply voltage rated value
  • of the solenoid
0.85…1.15
Auxiliary circuit:
Product function
  • inputs parameterisable
Yes
  • outputs parameterisable
Yes
Number of inputs
  • safety-related
8
  • not safety-related
0
Number of outputs
  • as contact-affected switching element / safety-related
  • 1-channel
1
  • 2-channel
0
  • as contact-less semiconductor switching element
  • safety-related / 2-channel
1
  • not safety-oriented / 2-channel
0
  • to the test of contact afflicated sensors
2
Short-circuit:
Design of the fuse link / for short-circuit protection of the contact afflicted switching element / requiredNH Typ 3NA, DIAZED Typ 5SB, NEOZED Typ 5SE
Installation/mounting/dimensions:
Type of mountingstandard rail
Widthmm45
Heightmm113
Depthmm124
Connections:
Product function / removable terminal for auxiliary and control circuitYes
Design of the electrical connection / for auxiliary and control current circuitspring-loaded terminals
Conductor cross-section that can be connected / for auxiliary contact
  • solid
mm²0.25…1.5
  • stranded wire
  • with conductor end processing
mm²0.25…1.5
  • without conductor final cutting
mm²0.25
AWG number / as coded connectable conductor cross-section
  • for auxiliary contact
20…16
Type of the connectable conductor cross-section / for auxiliary contacts
  • solid
2x (0.25 ... 1.5 mm²)
  • finely stranded
  • with conductor end processing
2x (0.25 ... 1.5 mm²)
  • without conductor final cutting
2x (0.25 ... 1.5 mm²)
Type of the connectable conductor cross-section / for AWG conductors
  • for auxiliary contacts
2x (20 ... 16)
safety Integrated Level / according to IEC 61508SIL3
Performance level (PL) / according to ISO 13849-1e
Category / according to EN 954-14
Probability of dangerous failure per hour (PFHD) / with high demand rate / according to EN 620611/h0.514E-8
Average probability of failure on demand (PFDavg)0.0000128 1/y
T1 value / for proof test interval or service life / according to IEC 61508a20
Stop category / according to DIN EN 60204-10 / 1
Cax online generator:

1 Units in Stock


Call for Availability

Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question